How to verify factory lighting energy use by shift

Exterior of the Ulpatek Filter Production Facility
Ulpatek Filter Production Facility from CANEL’s project archive.

Technical Guides

Prepared by
CANEL Elektrik
Published
Reading time
2 min

Define the metering boundary, shift records and acceptance scenarios when specifying lighting controls and energy monitoring for a factory.

A factory’s total electricity use cannot tell you how much its lighting consumed after a controls upgrade. Motors, ventilation and production equipment may all operate differently in the same period. Start the electrical tender by defining which lighting groups you will compare, which panels feed them and what the shift records should capture.

Match the metering boundary to the control groups

Show the lighting panel, meter and circuits covered on the same single-line diagram. Production, warehouse and office lighting may use the same control system while operating on different schedules. If the energy dashboard includes several types of load, identify them in the report. Matching the control group name to the panel and circuit identifiers makes changes in the meter readings easier to trace to the relevant group. See our guide to verifying panel-level energy data for more on checking metering points.

Record shifts, daylight and manual overrides

Record shift hours, weekend operation and any manual overrides for the baseline period. Where lighting is dimmed in response to daylight, record the operating conditions for both comparison periods. If an area operated a night shift before the upgrade and subsequently ran only during the day, comparing the totals directly could confuse changes in operating schedules with changes in the lighting system. The US Department of Energy’s measurement and verification guide illustrates how power draw and operating hours can be used in lighting retrofit calculations.

Specify functional testing and energy records in the tender

Ask tenderers to identify who supplies the controls and meters, connects field devices, checks timestamps and provides data exports. During acceptance, observe how the lights respond during a normal shift, when the area is unoccupied and when an operator uses an override. Check separately that the same period is available in the energy records. An acceptance sheet can capture the panel, circuit group, test time and observed result. Our guide to factory lighting automation covers examples of control scenarios.

How to read the CANEL project reference

CANEL’s Ulpatek Filter Facility project record documents medium- and low-voltage electrical infrastructure serving production and office areas. The shift-based measurement steps here are an example for future tenders and acceptance tests. For a factory upgrade, share the single-line diagram, lighting circuit schedule and operating hours with CANEL’s electrical contracting team to discuss the scope.